LDI 70 kN 120 kN 160 kN - Lant dublu de intindere pentru 110 kV
Poz | Componenta | Tip | Caracteristici Tehnice | Buc |
1 | Carlig | tip B 6,5/16 (B 8/16) | 160 kN | 1 |
2 | Ochi rasucit | tip OD16 | 160 kN | 2 |
3 | Jug simplu | tip JS 200/16 (JS 250/16) | 160 kN | 2 |
4 | Ochi simplu de suspensie | tip OSDr 16 (OSDr 20) | 120 (160) kN | 2 |
5 | Ansamblu corn II | - | 2 | |
6 | Izolator compozit | de 110 kV, tip BS | conform tabel 2 | 2 |
7 | Ansamblu corn I | - | 2 | |
8 | Nuca | tip NORV16 (NORV20) | 120 (160) | 2 |
9 | Clema de sustinere | tip TPDFc | 95 % UTS | 1 |
Zona | Tip izolator | I (mm) | L (mm) | ||||
II | CI-110-II-70-BS | 1129 | 1670 | ||||
CI-110-II-120-BS | 1217 | 1778 | |||||
CI-110-II-160-BS | 1258 | 1819 | |||||
III | CI-110-III-70-BS | 1197 | 1758 | ||||
CI-110-III-120-BS | 1285 | 1846 | |||||
CI-110-III-160-BS | 1326 | 1887 | |||||
IV | CI-110-IV-70-BS | 1299 | 1860 | ||||
CI-110-IV-120-BS | 1387 | 1948 | |||||
CI-110-IV-160-BS | 1428 | 1989 |
Obs. : * Distanta de eclatare k este conforma cu supratensiunile de trasnet si de comutatie stabilite de proiectantul (beneficiarul) liniei.